GENERAL
These completely assembled 5, 7-1/2 and 10 ton blower
units include a well insulated cabinet, a DX cooling coil with
copper tubes and aluminum fins, an expansion valve, a
distributor, throwaway filters, a centrifugal blower, a blower
motor contactor and a small holding charge of refrigerant-22.
Blower motors and adjustable drives are factory-installed on
all units.
The units are shipped in the vertical position ready for field
installation. For horizontal installation, reverse the solid
bottom panel and the return air duct flange on the front of
the unit.
INSPECTION
As soon as a unit is received, it should be inspected for
possible damage during transit. If damage is evident, the
extent of the damage should be noted on the carrier’s freight
bill. A separate request for inspection by carrier’s agent
should be made in writing.
RENEWAL PARTS
Refer to Parts Manual for complete listing of replacement
parts on this equipment for complete listing of replacement
parts. The forms referenced in this instruction may be
ordered from:
Publications Distribution Center
Unitary Products Group
P.O. Box 1592, York, PA. 17405
This instruction covers the installation and operation of
evaporator blower units. For information on the operation of
the matching condensing unit, refer to Forms 550.46-N1Y,
550.46-N2Y, 550.38-N1Y, 550.38-N6Y and 550.23-N1Y.
Installer should pay particular attention to the words: NOTE, CAUTION and WARNING. Notes are intended to clarify or make the installa-
tion easier.
Cautions are given to prevent equipment damage. Warnings are given to alert installer that personal injury and / or equipment
damage may result if installation procedure is not handled properly.
MODELS K2EU060A, K4EU090A, & K3EU120A
AIR COOLED
SPLIT-SYSTEM AIR CONDITIONERS
INSTALLATION INSTRUCTION
Supersedes: 550.23-N2Y (589)
550.23-N2Y (399)
035-16672
®
Seitenansicht 0
1 2 3 4 5 6 ... 15 16

Inhaltsverzeichnis

Seite 1 - INSTALLATION INSTRUCTION

GENERALThese completely assembled 5, 7-1/2 and 10 ton blowerunits include a well insulated cabinet, a DX cooling coil withcopper tubes and aluminum fi

Seite 2 - NOMENCLATURE

1-23/32 KNOCKOUT(Removed only whenElectric Heat Accessoryis used)36-1/88-1/213-1/43-7/817/8" HOLE W/BUSHINGIN REAR PANEL(For Low VoltageControl P

Seite 3 - INSTALLATION

All dimensions are in inches. They are subject to changewithout notice. Certified dimensions will be provided uponrequest.1-23/32 KNOCKOUT(Removed

Seite 4 - VERTICAL

POWER AND CONTROL WIRINGInstall electrical wiring in accordance with the latest NationalElectrical Code (NFPA Standard No. 70 and/or localregulations)

Seite 5 - - PHYSICAL DATA

Model BasicUnit1Nominal HeaterKW2Power SupplyVoltage3Full Load AmpsTotal Ampacity,AmpsMax. FuseSize4, AmpsMin. WireSize5, AWGMax. WireLength6, Ft.Heat

Seite 6 - 6 Unitary Products Group

550.23-N2Y14 Unitary Products Group

Seite 7

550.23-N2YUnitary Products Group 15

Seite 8 - AIR CFM

Unitary Products Group5005 York Drive, Norman, Oklahoma 73069Subject to change without notice. Printed in U.S.ACopyright  by York International Co

Seite 9 - TABLE 5

TABLE OF CONTENTSGeneral ... 1Renewal Parts...

Seite 10 - FIG. 12

LIMITATIONSThis unit must be installed in accordance with all nationaland local safety codes. If no local codes apply, installationmust conform to th

Seite 11 - FIG. 13

RIGGING AND HANDLINGBe careful when moving the unit. Do not remove anypackaging until the unit is near its final location.The packaging consists of a

Seite 12 - - TYPICAL FIELD WIRING

Hard drawn copper tubing should be used where noappreciable amount of bending around pipes or otherobstructions is necessary. Use long radius ells wh

Seite 13 - MAINTENANCE

CAUTION: Always puncture sealing caps and discs with asmall drill bit before unbrazing to prevent the pres-sure in the line from blowing them off.Befo

Seite 14 - 14 Unitary Products Group

NOTE: Refer to Figure 12 or 13 for minimum clearance re-quirements.SUPPLY AIR BLOWER ADJUSTMENTThe RPM of the supply air blower will depend on therequ

Seite 15 - Unitary Products Group 15

After the supply air blower motor is operating, adjust theresistances in both the supply and the return duct systemsto balance the air distribution th

Seite 16

inaccurate. To assure a dry coil, the refrigeration systemshould be de-activated while the test is being run.4. Knowing the pressure drop across a dr