GENERALModel D1EB units are factory assembled cooling only air condi-tioners designed for outdoor installation on a rooftop or a slab.Field-installed
10 Unitary Products Group035-16703-001-A-0202FIG. 3 - DIMENSIONS AND CLEARANCESCLEARANCES(Minimum)Front 12"Back 0"Left Side (Filter Access)
CoolingThe following sequences of operation are based on using astandard single-stage cooling thermostat.WITH POWER TO UNIT AND THERMOSTAT IN COOLINGM
12 Unitary Products Group035-16703-001-A-0202NORMAL MAINTENANCEWARNING:Prior to any of the following maintenance proce-dures, shut off all power to th
Unitary Products Group 13035-16703-001-A-0202FIG. 4 - TYPICAL WIRING DIAGRAM (208/230-1-60 POWER SUPPLY) POWER SUPPLY POWER SUPPLY 208/230-1-60 208/23
14 Unitary Products Group035-16703-001-A-0202FIG. 5 - TYPICAL WIRING DIAGRAM (230-3-60 POWER SUPPLY)
Unitary Products Group 15035-16703-001-A-0202L2L1POW ER SUPPLY W /O UTELEC HEAT 460-3-60O R 5 7 5 -3 -6 0USE COPPERCONDUCTORSONLYGNDLU GPOW ER SUPPLY
16 Unitary Products Group035-16703-001-A-0202TYPICAL WIRING DIAGRAM NOTESTYPICAL WIRING DIAGRAM LEGENDHTR 5 ELECTRIC HEATER (OPT. ACCSSRY:
Unitary Products Group5005 York Drive, Norman Oklahoma 73069Subject to change without notice. Printed in U.S.A.Copyright by York International Co
LIMITATIONSThese units must be installed in accordance with the followingnational and local safety codes.1. National Electrical Code ANSI/NFPS No. 70
CLEARANCESAll units require certain clearances for proper operation andservice. Refer to Figure 3 for the clearances required for com-bustion, constru
POWER AND CONTROL WIRINGField wiring to the unit must conform to provisions of the currentN.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances.Th
035-16703-001-A-0202Unitary Products Group 5MODELDEBPOWER SUP-PLYVOLTAGELIMITATIONS1COMPRESSORCOND.FANMOTOR,FLASUPPLYAIRBLOWERMOTOR,FLAMINIMUMCIRCUITA
035-16703-001-A-02026 Unitary Products GroupDEBPOWERSUPPLYCOMPRESSORCOND.FANMOTORFLASUPPLYAIRBLOWERMOTOR,FLAELECTRIC HEAT ACCESSORYMINIMUMCIRCUITAMPAC
Checking Supply Air CFMTo check the supply air CFM after the initial balancing has beencompleted:1.Remove the two ¼ inch dot plugs in the duct panel.2
8 Unitary Products Group035-16703-001-A-0202TABLE 7 - SUPERHEAT CHARGING TABLE FOR MODEL D1EB024OUTDOORTEMPERATURE(F)SUPERHEAT AT COMPRESSOR SUCTION (
Unitary Products Group 9035-16703-001-A-0202TABLE 10 - SUPERHEAT CHARGING TABLE FOR MODEL D1EB042OUTDOORTEMPERATURE(F)SUPERHEAT AT COMPRESSOR SUCTION