272313-UIM-A-0407HIGH EFFICIENCYTUBULAR HEAT EXCHANGER SERIESMODELS: PT9-UP / FC9T-UP / FL9T-UP(Two Stage Upflow)40 - 120 MBH INPUT(11.7 - 35.1 KW) IN
272313-UIM-A-040710 Unitary Products GroupFor additional connection diagrams for all UPG equipment refer to “Low Voltage System Wiring” document avail
272313-UIM-A-0407Unitary Products Group 11 FIGURE 6: Thermostat Chart - HPHP23 Two Stage H/P - H*5B, YZE - w/Two Stage Furnace, 2 Stage Cooling Ready
272313-UIM-A-040712 Unitary Products GroupACCESSORY CONNECTIONSThe furnace control will allow power-switching control of various acces-sories. Refer t
272313-UIM-A-0407Unitary Products Group 13Twinning OperationHeating - On a call for low-stage heat (W1 signal) from the wall thermo-stat, both furnace
272313-UIM-A-040714 Unitary Products GroupCOMBUSTION AIR/VENT PIPE SIZINGThe size of pipe required will be determined by the furnace model, thetotal l
272313-UIM-A-0407Unitary Products Group 15*. Vent pipe size must be increased to 3” diameter after connection to furnace on this model.IMPORTANT: Acce
272313-UIM-A-040716 Unitary Products GroupVENT CLEARANCES† A vent shall not terminate directly above a sidewalk or paved driveway that is located betw
272313-UIM-A-0407Unitary Products Group 17VENT SYSTEMThis furnace is certified to be installed with one of two possible ventconfigurations.1. Horizont
272313-UIM-A-040718 Unitary Products Group COMBUSTION AIR SUPPLYAll installations must comply with Section 5.3, Air for Combustion andVentilation of t
272313-UIM-A-0407Unitary Products Group 19A confined space is an area with less than 50 cu.ft (1.42 m3) per 1,000Btu/hr (0.2928 kW) input rating for a
272313-UIM-A-04072 Unitary Products GroupSPECIFIC SAFETY RULES AND PRECAUTIONS1. Only Natural gas or Propane (LP) gas are approved for use withthis fu
272313-UIM-A-040720 Unitary Products GroupVent and Supply (Outside) Air Safety Check ProcedureFollow the procedure in ANSI Z223.1 National Fuel Gas Co
272313-UIM-A-0407Unitary Products Group 21CONDENSATE DRAINThe condensate trap must be filled with water before putting the furnaceinto operation. Perf
272313-UIM-A-040722 Unitary Products GroupTOOLS AND INFORMATION THAT WILL BE REQUIRED IN ORDER TO PROPERLY PERFORM THE FURNACE STARTUP PROCEDURE.1. Ca
272313-UIM-A-0407Unitary Products Group 23In the USA use the following formula to calculate the furnace input.For natural gas multiply the heat conten
272313-UIM-A-040724 Unitary Products GroupIMPORTANT: The inlet gas pressure operating range table specifieswhat the minimum and maximum gas line press
272313-UIM-A-0407Unitary Products Group 25ADJUSTMENT OF TEMPERATURE RISEThe temperature rise, or temperature difference between the return airand the
272313-UIM-A-040726 Unitary Products GroupFURNACE CONTROL DIAGNOSTICSThe furnace has built-in, self-diagnostic capability. If a system problemoccurs,
272313-UIM-A-0407Unitary Products Group 27NOTES:1. Airflow expressed in standard cubic feet per minute (CFM) and in cubic meters per minute (m3/min).2
272313-UIM-A-040728 Unitary Products GroupAPPLYING FILTER PRESSURE DROP TO DETERMINE SYSTEM AIRFLOWTo determine the approximate airflow of the unit wi
272313-UIM-A-0407Unitary Products Group 29SECTION X: WIRING DIAGRAM FIGURE 27: Wiring Diagram
272313-UIM-A-0407Unitary Products Group 3INSPECTIONAs soon as a unit is received, it should be inspected for possible dam-age during transit. If damag
272313-UIM-A-040730 Unitary Products GroupNOTES
272313-UIM-A-0407Unitary Products Group 31NOTES
Subject to change without notice. Printed in U.S.A. 272313-UIM-A-0407Copyright © by York International Corp. 2007. All rights reserved. Supersedes: 1
272313-UIM-A-04074 Unitary Products GroupSECTION II: DUCTWORKDUCTWORK GENERAL INFORMATIONThe duct system’s design and installation must:1. Handle an a
272313-UIM-A-0407Unitary Products Group 51. The Air Temperature Rise is determined by subtracting the ReturnAir Temperature Reading from the Supply Ai
272313-UIM-A-04076 Unitary Products GroupRESIDENTIAL AND NON HUD MODULAR HOME RETURN PLENUM CONNECTIONReturn air may enter the furnace through the sid
272313-UIM-A-0407Unitary Products Group 7NOTES: 1. Air velocity through throwaway type filters may not exceed 300 feet per minute. All velocities over
272313-UIM-A-04078 Unitary Products GroupGAS ORIFICE CONVERSION FOR PROPANE (LP)This furnace is constructed at the factory for natural gas-fired opera
272313-UIM-A-0407Unitary Products Group 9Annual Fuel Utilization Efficiency (AFUE) numbers are determined in accordance with DOE Test procedures.Wire