FILTER PERFORMANCE
The airflow capacity data published in Tables 8 & 9 repre-
sents blower performance WITHOUT filters. To determine the
approximate blower performance of the system, apply the fil-
ter drop value for the filter being used or select an appropri-
ate value from the Table 10.
NOTE: The filter pressure drop values in Table 10 are typical
values for the type of filter listed and should only be used as a
guideline. Actual pressure drop ratings for each filter type
vary between filter manufacturer.
AIRF LOW D ATA - DOW NF LOW /H ORI ZON TA L MOD ELS: P*D H/ G9T-DH /F G9-DH
MODELS
Input/Output/Airflow/
ca bine t
S PEE D TAP
EX TERNAL STATIC PRE SSURE, I NCHES WC
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0. 8 0.9 1.0
40 / 37 / 1000 / "A
HIG H 14 00 1 35 0 13 00 12 50 1 20 0 11 35 10 60 97 0 880 7 65
MED-HI GH 97 0 955 9 45 93 5 91 5 8 85 8 40 78 0 705 6 00
MED-LOW 77 0 760 7 50 73 5 71 0 6 80 6 40 59 5 535 4 50
LOW 595 585 575 560 540 520 485 455 400 270
60 / 5 5 / 1 200 / "B"
80 / 75 / 1200 / "B
HIGH 1605 1590 1570 1545 1510 1470 1415 1360 1285 1205
MED 12601245122512051180 1150111010651005930
LOW 930 915 895 880 860 835 810 770 695 620
80 / 75 / 1600 / "C
HIGH 2030 1980 1925 1870 1830 1755 1675 1600 1515 1435
MED 1505149014751460144014201380134012801215
LOW 1295 1285 1260 1240 1215 1190 1160 1130 1080 1000
100 / 95 / 2000 / "C
HIGH 2330 2270 2200 2130 2060 1985 1890 1810 1710 1625
MED 2005196519201870182017501680160015001395
LOW 1580 1560 1535 1510 1480 1440 1390 1325 1255 1175
1 20 / 11 2 / 20 00 / "D
HIGH 2335 2280 2215 2145 2065 2000 1905 1820 1720 1620
MED 1975193018851830177517201655158015001400
LOW 1515 1495 1475 1450 1415 1380 1330 1275 1210 1135
Airflow expressed in standard cubic feet per minute.
Notes: 1. Air filter installed. All filters must be high velocity, cleanable type.
2. M oto r voltag e a t 11 5 V.
Table 10:
FILTER PERFORMANCE - PRESSURE DROP INCHES W.C.
Airflow Range
Minimum Openi ng Size
(in.
2
)
Filter Type
Disposable
Hogs Hair
*
Pleated
1 Opening 2 O penings 1 Opening 2 O penings 1 Opening 2 O penings 1 Opening 2 Openings
0 - 750 230 0.0 1 0.0 1 0.1 5
751 - 10 00 33 0 0.0 4 0.0 3 0.2 0
1001 - 1250 330 0.0 8 0.0 7 0.2 0
1251 - 1500 330 0.0 8 0.0 7 0.2 5
1501 - 1750 380 658 0.14 0.08 0.13 0.06 0.30 0.17
1751 - 2000 380 658 0.17 0.09 0.15 0.07 0.30 0.17
2001 & Above 46 3 658 0.17 0.09 0.15 0.07 0.30 0.1 7
*.
Hogs Hair Filters are the type supplied with furnace (if supplied).